Caleffi QuickSetter 132992A Balancing Valve With Flow Meter, 2 in Nominal, FNPT, 150 psi, 12 to 50 gpm, Brass Body

CALEFFI 132992A 2" QUICK-SETTER BALANCING VALVE W/ FLOW METER

Hydronic Balancing Valves }

Caleffi QuickSetter 132992A Balancing Valve With Flow Meter, 2 in Nominal, FNPT, 150 psi, 12 to 50 gpm, Brass Body

3289010 Product ID:3289010
Famous Supply
  • Dimensions: 7 in H
  • Media: Water/Glycol
  • Series: 132
  • Softgoods Material: EPDM Seal
  • Temperature Rating: 14 to 230 deg f
  • Trim Material: PTFE
  • Nominal Size: 2 in
  • End Style: FNPT
  • Pressure Rating: 150 psi
  • Flow Rate: 12 to 50 gpm
  • Body Material: Brass
The 132 series balancing valve accurately sets the flow rate of heating and cooling transfer fluid supplied to fan coils and terminal units or where flow balancing is required in solar thermal systems. Proper hydronic system balancing ensures that the system operates according to design specifications, providing satisfactory thermal comfort with low energy consumption. The flow meter is housed in a bypass circuit on the valve body and can be shut off during normal operation. The flow meter permits fast and easy circuit balancing without added differential pressure gauges and reference charts. The balancing valve is furnished with a preformed insulation shell to optimize thermal performance for both hot and cold water systems.
  • Features
  • Standards & Approvals
  • Includes
Direct reading of flow rate
No sight gauge clouding or scaling
Rotatable valve for flow rate adjustment
Graduated scale flow meter with magnetic movement flow rate indicator
ICIM Certified
FM 21654
Flow Meter