Honeywell Aquatrol AQ25142B/U Boiler Reset Controller, Supply/Return Sensor, DIP Switch User Interface, 4 Zones, 24 VAC 0.5 A 12 VA Boiler Output, Import

HONEYWELL AQ25142B BOILER RESET CONTROLLER WITH DHW PRIORITY FOR 4 ZONES OF PUMPS OR 2-WIRE VALVES

Hydronic Boiler Control }

Honeywell Aquatrol AQ25142B/U Boiler Reset Controller, Supply/Return Sensor, DIP Switch User Interface, 4 Zones, 24 VAC 0.5 A 12 VA Boiler Output, Import

3167033 MFG #: AQ25142B Product ID:3167033
Famous Supply
  • Dimensions: 8 in H x 16-1/2 in W x 3-3/8 in D
  • Electrical Connections: Wire-Clamp Screw Terminal
  • Lead Length: 10 ft
  • Power Rating: 38 va
  • Wire Size: 2 x 14 AWG
  • Sensor Type: Supply/Return
  • User Interface: DIP Switch
  • Number of Zones: 4
  • Boiler Output: 24 VAC 0.5 A 12 VA
  • Domestic/Import: Import
Honeywell AQ251 AQUATROL boiler reset controls for single temperature, residential hydronic heating systems, provide energy-efficient outdoor-temperature compensated control to convert single zone heating system or upgrade relay-logic zoning systems.
  • Features
  • Standards & Approvals
  • Application
5 to 90% RH non-condensing operating humidity
24 VAC class II (input on control and zoning modules) R-C input
Intuitive and accessible programming interface and central program of zone set points and setback
Zoning control for up to four zones and can be up to 64 zones using expansion panels
Boiler short cycling protection, boiler post purge and boiler shock prevent from cold water returning to boiler
Domestic hot water priority and priority override protection, as well as an automated test and purge feature
Test and purge feature for quick start-up and simplified troubleshooting
38 VA and 24 VAC Class II R-C output
AQ1000 series 2-wire communicating thermostats and most digital thermostats thermostat compatibility
7 day, up to 2 setback periods/day setback program
Pumps or 2-wire valves zoning devices controlled
Supply: OFF, 120 to 225 F max boiler control temperature
80 to 210 deg F boiler design temperature
-60 to 32 deg F Outdoor low design control temperature
80 to 180 deg F return min control temperature
OFF, 10 sec to 30 min(factory default is 30 sec) boiler heat post purge
30 sec per 2 weeks of space heating inactivity pump/valve exercise
Demand input: Heat demand (thermostat R-W) auxiliary demand and DHW demand external dry contacts connection only
B-B communication bus terminals: low voltage, Class II, 2-wire polarity-insensitive, digital communicating link to other control or zoning modules
Zone module thermostat input: low voltage, Class II, 2-wire polarity-insensitive, digital communicating with power link to AQ1000 series thermostat
CSA C/US Certified to CSA and UL Standards File #LR76030
Boiler Reset Control For Hydronic Zoning System